DN-6859:A • 10/10/06 — Page 1 of 4
ONYX® Series
Panel Circuit Modules
Peripheral Devices
DN-6859:A • G-300
General
Panel Circuit Modules provide NOTIFIER’s NFS-640 with up
to 64 panel (main FACP) circuits, and the NFS-3030 with up to
96 panel circuits. Switches are provided for each circuit to pro-
vide manual ON/OFF of each output circuit.
NFS-640: Supports up to eight output modules — each with
an optional expander. This includes the ICM-4RK, CRM-4RK,
VCM-4RK, and DCM-4RK (no expander option).
NFS-3030: Supports up to twelve input or output modules.
This includes the IZM-8RK (for NFS-3030 only; with or without
Class A option), ICM-4RK, CRM-4RK, VCM-4RK, or DCM-
4RK (no expander option for DCM-4RK).
Four Form-C (SPDT) relay contacts are available on the
CRM-4RK Control Relay Module to control auxiliary
devices. The CRE-4 Control Relay Expander will provide
four additional Form-C (SPDT) relay contacts for a total of
eight.
The ARM-4 Auxiliary Relay Module is used for high power
switching and may be slaved to a CRM-4RK/CRE-4 mod-
ule.
The ICM-4RK Notification Appliance Circuit Module provides
four Style Y (Class B) or Style Z (Class A) supervised
audio/visual alarm Notification Appliance Circuits, expand-
able to eight with the ICE-4. The CRE-4 can be used (one
expander option per ICM-4RK) to provide the ICM-4RK with
four additional SPDT control relays.
The IZM-8RK provides eight Class B (Style B) Initiating Zones
(Initiating Device Circuits) that can be selected for Class A
(Style D) with the addition of an IZE-A expander module.
Each IZM-8RK/IZE-A zone can be programmed for a vari-
ety of initiating devices functions including: dry contact
input, two-wire smoke detection, flow, tamper, non-fire, and
many others. Note: IZM-8RK/IZE-A for NFS-3030 only.
The VCM-4RK Voice Control Module provides four Style Y
(Class B) or Style Z (Class A) speaker circuits, four Style Y
(Class B) telephone circuits, eight manual select switches
and indicators. VCE-4 Voice Control Expander adds four
circuits to VCM-4. Note: VCM-4/VCE-4 combination must
be eight speaker or eight phone circuits.
The DCM-4RK Dual Channel Module provides four Class B
(Style Y) or Class A (Style Z) speaker circuits plus four
channel A/B select relays. Not expandable.
Applications and Features
FOR CRM-4RK, CRE-4, AND ARM-4:
The CRM-4RK provides up to four Form-C (SPDT) relay con-
tacts for auxiliary control functions.
The CRE-4 expands the CRM-4RK to a total of eight Form-C
(SPDT) relay contacts.
The ARM-4 module can be used when greater load switching
capability is required. The ARM-4 is slaved to a CRM-4RK or
CRE-4 module.
Four Form-C (SPDT) relay contacts.
May be expanded to eight Form-C relay contacts.
20 amp N.O. (normally open contacts) and 10 amp N.C. (nor-
mally closed contacts) switching with ARM-4.
Green LEDs to indicate relay activation or I/O mapping.
Amber LEDs to indicate relay disabled, module fault or system
communications failure.
Control switch for Manual On/Off of each relay.
FOR ICM-4RK AND ICE-4:
Each ICM-4RK provides four supervised audio-visual alarm
notification circuits. The ICM-4K may be expanded with one of
the following:
a) Use the ICE-4 to provide four additional Style Y (Class B) or
Style Z (Class A) supervised alarm indicating circuits; OR...
b) Use the CRE-4 to provide four SPDT control relays.
Four alarm notification circuits, expandable to eight.
Supervised, power-limited outputs, suitable for use with lim-
ited energy cable.
Outputs resound on subsequent alarm.
Outputs may be programmed as silenceable or nonsilence-
able.
Each circuit is provided with a switch for manual activation/
deactivation.
LEDs for indication of circuit activation and trouble.
Separate input connections for audible-visual circuit power.
FOR IZM-8RK AND IZE-A:
The IZM-8RK Initiating Zone (Initiating Device Circuit) Module
provides eight Style B (Class B) alarm initiating or supervisory
circuits. The IZE-A Initiating Zone Expander, when used with
the IZM-8RK, provides eight Style D (Class A) alarm initiating
or supervisory circuits.
Eight zones Style B (Class B) with IZM-8RK; eight zones
Style D (Class A) with both IZM-8RK and IZE-A.
6859crm4.wmf
Control Relay Module (CRM-4RK)
Page view 0
1 2 3 4

Summary of Contents

Page 1 - ONYX® Series

DN-6859:A • 10/10/06 — Page 1 of 4ONYX® SeriesPanel Circuit ModulesPeripheral DevicesDN-6859:A • G-300GeneralPanel Circuit Modules provide NOTIFIER’s

Page 2 - Construction

Page 2 of 4 — DN-6859:A • 10/10/06• Powered loop allows the use of two-wire smoke detectors/devices. Alarm verification is optional, although if selec

Page 3 - Specifications

DN-6859:A • 10/10/06 — Page 3 of 4InstallationExpansion modules mount to the back of the master moduleswith the hardware provided.The master module mo

Page 4 - Product Line Information

Page 4 of 4 — DN-6859:A • 10/10/06NOTIFIER® and ONYX® is a registered trademark of HoneywellInternational Inc. ©2006 by Honeywell International Inc. A